Delta · MS300Fault Code ovWarning
Delta MS300 — ov DC Bus Overvoltage
Occurs when the DC bus voltage exceeds the limit. Fast deceleration and regenerative energy are the main causes.
Updated: 2026-07-05
Symptoms
- ov trip on deceleration
- Recurs on high-inertia loads
- Occurs when supply is high
Probable Causes
- Too-short decel time (Pr.01-13)
- No/faulty brake resistor
- Supply overvoltage
Checkpoints
- Increase decel time (Pr.01-13)
- Measure the brake resistor and connection
- Check supply voltage
Solution
First extend the decel time. For frequent/fast stops a brake resistor is mandatory.