Schneider Electric · Altivar ATV320Fault Code OLFWarning

Schneider Altivar — OLF Motor Overload

Raised when the motor thermal protection reports overload. Increased mechanical load or wrong motor-current setting is the cause.

Updated: 2026-07-05

Symptoms

  • OLF under long/high load
  • Recurs at a specific operating point
  • Motor heating

Probable Causes

  • Mechanical overload / jam
  • Wrong motor rated current (ITH) setting
  • Insufficient motor cooling

Checkpoints

  • Measure motor current and mechanical load
  • Verify the ITH (motor thermal current) setting
  • Check the motor fan

Solution

If the mechanical load is normal, a wrong ITH setting is a common false-alarm cause; correct it to the motor nameplate.