Delta MS300 — GFF Ground Fault

Raised when leakage current to ground is detected on the output. Motor/cable insulation breakdown is the main cause.

Updated: 2026-07-05

Symptoms

  • GFF trip on start
  • Frequent with damp/old motors
  • Tends to occur with long cables

Probable Causes

  • Motor winding insulation breakdown
  • Ground leakage in the motor cable
  • Moisture/contamination

Checkpoints

  • Disconnect the motor; megger phase-to-ground
  • Measure the motor cable separately
  • Check for moisture/dirt in terminals and junction box

Solution

A ground fault is an electrical-safety risk. Do not restart the drive before replacing the motor/cable with failed insulation.