Schneider Altivar — SCF Output Short Circuit

Raised when a phase-to-phase or phase-to-ground short is detected on the output. Motor/cable or output stage related.

Updated: 2026-07-05

Symptoms

  • SCF and stop on start
  • Immediate fault with motor connected
  • Fault may change when cable removed

Probable Causes

  • Short in the motor cable
  • Motor winding insulation breakdown
  • Output stage (IGBT) short

Checkpoints

  • Megger the motor and cable separately
  • Check the IGBT with diode-test
  • Inspect the output terminals

Solution

If an IGBT short is confirmed, the gate-driver circuit must also be checked before fitting a new module; otherwise it will fail too.