Schneider Electric · Altivar ATV320Fault Code OCFCritical
Schneider Altivar — OCF Overcurrent
Occurs when the drive output current suddenly exceeds the limit. Short accel, mechanical jam or motor/cable issues trigger it.
Updated: 2026-07-05
Symptoms
- OCF on acceleration or load impact
- Immediate trip on mechanical jam
- Occurs with the motor connected
Probable Causes
- Too-short acceleration time (ACC)
- Mechanical jam / sudden load
- Motor cable short
- Wrong motor parameters
Checkpoints
- Increase acceleration time (ACC)
- Manually check the mechanical system
- Measure motor cable insulation
Solution
If mechanics and cabling are healthy, the output stage (IGBT) is tested in the lab.
Related Products
Related Faults
Related Topics
Facing the same issue?
Send your faulty board to our lab or consult our expert team. Free pre-analysis.
+90 543 855 16 44 · info@elkarotomasyon.com