Skip to content
ELKAR
Yaskawa · A1000Fault Code oL2Warning

Yaskawa A1000 — oL2 Motor Overload

Raised when electronic thermal protection calculates motor overload. Mechanical load or wrong motor-current setting is the cause.

Updated: 2026-07-05

Symptoms

  • oL2 under long/high load
  • Motor heating
  • Recurs at a specific operating point

Probable Causes

  • Mechanical overload
  • Wrong motor rated current (E2-01) setting
  • Long low-speed operation

Checkpoints

  • Measure motor current and load
  • Verify the E2-01 motor-current setting
  • Check mechanical resistances

Solution

If load is normal, correct E2-01 to the nameplate; review the L1 motor-protection settings.