ABB ACS580
The drive trips on overcurrent (2310) immediately at start; the fault persists even when tested without a motor.
Faulty — board out of service
Repaired — tested under load
Fault
The drive trips on overcurrent (2310) immediately at start; the fault persists even when tested without a motor.
Analysis
The fault persisting in a no-motor test pointed to the drive output stage. A diode-test measurement found a phase-to-DC short in one IGBT arm.
Repair Steps
- 1Fault confirmation
All IGBT arms and body diodes measured with diode-test.
- 2Gate-driver check
Gate resistors, opto-isolator and supply rails verified.
- 3Component replacement
Faulty IGBT module and damaged driver-circuit parts replaced with original equivalents.
- 4Test under load
Board verified under load with current and heat profile.
Changed Components
- IGBT power module
- Gate-driver gate resistors
- Opto-isolator
Test Result
Run under load for 30 min; balanced current, normal heating. 2310 did not recur.