Siemens SINAMICS G120

The drive trips on undervoltage (F30003) under load; noticeable ripple observed on the DC-link voltage.

Duration: 2-3 business daysUpdated: 2026-07-07
Before

Faulty — board out of service

After

Repaired — tested under load

Fault

The drive trips on undervoltage (F30003) under load; noticeable ripple observed on the DC-link voltage.

Analysis

Mains and input phases were healthy. DC-link ripple and bus collapse under load pointed to aged electrolytic capacitors. ESR measurement showed high internal resistance.

Repair Steps

  1. 1
    Mains/input verification

    Input phases and rectifier found healthy.

  2. 2
    Capacitor measurement

    DC-link capacitors measured with ESR meter; high ESR found.

  3. 3
    Recap

    Capacitors replaced with new ones of the original value/rating.

  4. 4
    Test under load

    DC-link ripple returned to normal; F30003 did not recur.

Changed Components

  • DC-link electrolytic capacitors
  • Balancing resistors

Test Result

DC link stable under load; ripple within manufacturer tolerance.

This is an illustrative repair flow that shows the process; no real customer/board information is shared.